This new generation of transformer-less UPS responds to all major concerns of IT and facility managers. As saving costs and 100 percent uptime are their top priorities, PowerScale offers the lowest cost of ownership of any UPS system by providing energy efficiency, scalable flexibility, highest availability and easy serviceability.
GENERAL DATA |
|
System power range |
10 kVA – 1000 kVA |
UPS frame rated power |
10/9-15/13.5-20/18-25/22.8-30/27-40/36-50/45 kVA/kW |
UPS output rated PF |
0.9 |
Max. no of parallel frames |
Up to 20 units |
Wiring |
3ph + N + PE |
UPS type |
Standalone tower |
Topology |
True online double conversion |
INPUT |
|
Nominal input voltage |
220/380, 230/400, 240/415 VAC |
Voltage range |
150/204 - 264/460 VAC (load dependent) |
Frequency range |
35-70 Hz |
Current THD at 100% load |
≤3% |
Power Factor at 100% load |
≥0.99 |
OUTPUT |
|
Rated output voltage |
220/380, 230/400, 240/415 VAC |
Voltage THD (with linear load) |
<2% |
Frequency |
50 or 60 Hz (selectable) |
EFFICIENCY |
|
Online double conversion |
Up to 95.5% |
Eco-mode |
98% |
COMMUNICATIONS |
|
User interface |
LCD + mimic diagram |
Communication ports |
USB (optional), RS-232, SNMP slot, potential-free contacts (optional) |
Software |
Monitoring and shutdown software available as option |
COMPLIANCY |
|
Safety |
IEC/EN 62040-1 |
EMC |
IEC/EN 62040-2 |
Performance |
IEC/EN 62040-3 |
Manufacturing |
ISO 9001:2008, ISO 14001:2004 |