MegaFlex DPA - The best in power protection

 

MegaFlex DPATM is designed for critical high-density computing environments across private and public enterprise, as well as data centers for colocation, hosting cloud and telecommunications.

 

The modular UPS is based on ABB’s decentralized parallel architecture (DPA™). This innovative system means every UPS module is practically its own UPS with all the essential functional units needed for independent operation.

 

The on-line double conversion UPS provides the best power protection for your critical infrastructure from 250 kW to 1,500 kW. 


GENERAL DATA

UPS frame rated power

1000 kW / 1500 kW

UPS module rated power

250 kW

UPS output rated PF

1.0

Max no of parallel frames

Up to 4 frames 

Max no of parallel modules across frames

Up to 24 modules

Max system power

6000 kW

Wiring

3ph + N + PE (4W), 3ph + PE (3W)

UPS type

Modular (DPA)

Topology

Online double conversion

INPUT

Nominal input voltage

220/380, 230/400, 240/415 VAC

Voltage range

30% at partial loads

Frequency range

35 – 70 Hz

Current THD at 100% load

<4%

Power Factor at 100% load

0.99

OUTPUT

Rated output voltage (load dependent)

220/380, 230/400, 240/415 VAC 

Voltage THD (with linear load)

± 1%

Rated frequency

50 or 60 Hz (selectable)

EFFICIENCY

Double conversion

Up to 97.4% (50% rated load);
> 97% (25 % rated load)

Eco-mode

Up to 99%

COMMUNICATIONS

User interface

Module level LCD + mimic diagram, system graphical display

Communication ports

USB, RS-232, programmable potential-free contacts, ABB network card

Software

Monitoring and shutdown software available as option

 

The MegaFlex DPA UPS offering

Flexible approach

  • Easily scalable solutions
  • Up to 1,500 kW power protection in a single UPS with add-on modules
  • Redundant power capabilities: 1,000 kW N+1, 1,250 kW N+1
  • Collaborative, customer-centered approach

Optimized efficiency

  • Minimized energy losses, heat dissipation and electricity cost in double conversion or eco mode
  • Smart load-sharing optimizes energy consumption
  • Optimized system efficiency under low load conditions with ABB Xtra VFI
Reliable operations
  • DPA™ technology maximizing power availability
  • Online-swappable power modules for continuous uptime
  • Automatic isolation of any faulty power module
  • Fault-tolerant UPS design for uninterrupted power
  • Ease of operation with local and remote real-time monitoring

Simple installation and serviceability

  • Plug-in power modules support easy, safe connections
  • Pre-engineered power frames eliminate wiring entirely
  • Cleans and optimizes incoming power
  • Automatic self-configuration and testing minimizes human inter