Here is the detailed introduction of the **ABB ACS880-01-293A-3** frequency converter, organized by technical parameters, features, and applications:
### **1. Model Breakdown**
- **ACS880**: ABB's all-in-one drive series for industrial and heavy-duty applications.
- **01**: Single drive module design (standalone cabinet/wall-mounted).
- **293A**: Rated output current 293A.
- **3**: Voltage level (typically 400V AC, verify via nameplate).
### **2. Key Parameters**
| **Item** | **Specification** |
|------------------------|----------------------------------|
| **Rated Power** | ~160kW (estimated at 400V) |
| **Output Current** | 293A (continuous) |
| **Overload Capacity** | 150% for 60 seconds |
| **Input Voltage** | 380-500V AC, 3-phase 50/60Hz |
| **Protection Rating** | IP21 (standard) or IP54 (optional cabinet) |
| **Cooling Method** | Air-cooled (standard) |
### **3. Core Features**
- **Direct Torque Control (DTC)**: High-precision motor control with fast dynamic response, ideal for high-impact loads (e.g., crushers, presses).
- **Built-in Application Macros**: Pre-configured parameter sets for quick setup of pumps, fans, conveyors, etc.
- **Safety Functions**: Integrated STO (Safe Torque Off), SS1 (Safe Stop 1), compliant with SIL3/PLe standards.
- **Energy Optimization**: Automatic motor power adjustment, saving up to 30% energy (application-dependent).
### **4. Typical Applications**
- **Heavy Industry**: Mining crushers, metallurgical rolling mills.
- **Material Handling**: Large belt conveyors, hoists.
- **Process Control**: High-pressure water pumps, centrifugal compressors.
### **5. Communication & Expansion**
- **Protocol Support**: Profibus DP, Modbus RTU, EtherNet/IP (requires optional adapter).
- **Expansion Modules**: Optional I/O extension cards, encoder interface cards.
### **6. Options & Certifications**
- **Filters**: Standard DC reactor, optional harmonic filter (THD <5%).
- **Certifications**: CE, UL, cUL (North American market).
### **Important Notes**
- **Installation Environment**: Ambient temperature ≤40°C, altitude <1000m (derating required for higher elevations).
- **Maintenance**: Regularly clean air channels; capacitor inspection recommended every 2 years.
If you need this product, feel free to contact us!